Ia Aukuso, na alu atu ai le au tekinisia ina ua uma ona faatau atu a HV Hipot i Xiangyang.O le fa'amoemoega o lenei malaga o le tu'uina atu lea o 'au'aunaga fa'atosina eletise mo Xiangyang Power Supply Company.
A maeʻa ona taunuʻu i le nofoaga, faatasi ai ma le fesoasoani ma le galulue faʻatasi a le tagata faʻatau, o le faʻapipiʻiina o le uila eletise eletise eletise o le a faʻatinoina.
I luga o le saite debugging o GDCY-400kV uila eletise eletise
Fa'avasega le mamao o polo i luga ole laiga: fa'avasega le mamao ole polo ma le fa'avasegaina ole mamao ole polo chopper (3000/200/fua)
Su'ega i luga ole laiga: 30KV lelei ma le lelei polarity su'ega e tele (fa'afeiloa'i T1=1.2±30%/T2=50±20%us/TC=2 i le 6us)
Su'ega malosi i luga o le 'upega tafaʻilagi: faʻamauina voltage 80% gaioiga
A'oa'oga fa'apitoa ma fa'agaioiga i luga ole laiga:
Fa'ata'ita'iga a tagata fa'atau - su'ega fa'ata'ita'iga fa'ata'ita'iga o oloa: 10KV power transformer
1. Su'ega galu atoa
Su'ega mana'oga: su'ega voltage 75KV, waveform taimi T1=1.2±30%/T2=50±20%us
Fa'atonuga o fanua: fa'aogaina le lua-laasaga voluma gaosiga
Fa'atonuga o galu i luga ole laiga:
Tete'e ulu o galu: 150Ω mo le tulaga muamua, 500Ω mo le tulaga lona lua (2 1KΩ i le tutusa)
Tete'e o le si'usi'u: 1st stage 45Ω, 2nd stage 45Ω
Fa'atinoga o su'ega ma fa'agāluega:
2. Su'ega tipi
Su'ega mana'oga: su'ega voltage 85KV, taimi ulu galu T1=1.2±30%, taimi tipi TC=2 i le 6us
Fa'atonuga o fanua: fa'aogaina le lua-laasaga voluma gaosiga
Fa'atonuga o galu i luga ole laiga:
Tete'e o le ulu o galu: Laasaga 1 75Ω, Laasaga 2 500Ω (2 1KΩ e tutusa)
Tete'e o le si'usi'u: 1st stage 45Ω, 2nd stage 45Ω
Fa'atinoga o su'ega ma fa'agāluega:
A maeʻa lenei faʻasologa o aʻoaʻoga, o loʻo i ai i le tagata faʻatau se malamalamaaga loloto o le seti atoa o meafaigaluega, lea e faʻamalosia atili ai le tagata faʻatau i le gaioiga moni!