GDCO-301 Faiga Fa'ainitaneti o le Mata'ituina o le Ta'amilosaga I luga o le Uaea
O uaea i luga a'e o le 35kV e masani lava o uaea e tasi-autu ma fa'aofuofu u'amea.Talu ai o le u'amea u'amea o le uaea tasi-autu o lo'o fa'apipi'iina i le laina mageta e fa'atupuina e le AC o lo'o i totonu o le uaea autu, o pito e lua o le tasi-core cable o lo'o i ai se voltage fa'aoso maualuga.O le mea lea, e tatau ona faia ni faiga fa'avae talafeagai e fa'atumauina ai le voluma fa'aoso i totonu o le va'aiga saogalemu (e masani lava e le sili atu i le 50V, ae le sili atu i le 100V fa'atasi ai ma faiga saogalemu).E masani lava, o le u'amea u'amea o le laina pu'upu'u tasi-autu uaea e fa'avae sa'o i le tasi pito ma fa'avae i le va po'o le puipuiga o le puipuiga i le isi pito.O le u'amea u'amea o le laina umi laina tasi-autu uaea e fa'avaeina i le tolu-vaega vaega fa'alava-so'oga.E tusa lava po o le a le ituaiga auala faʻavae e faʻaaogaina, e manaʻomia le faʻamalama lelei.Pe a faaleagaina le insulation o le uaea, o le faaofuofu uamea o le a faavae i le tele o itu, lea o le a faatupuina ai le tafe o le taimi nei, faateleina le leiloa o le faaofuofu, aafia ai le gafatia tauave o le uaea i le taimi nei, ma e mafua ai ona mu le uaea. ona o le vevela tele.I le taimi lava e tasi, faʻamautinoa le maualuga o le uʻamea faʻapipiʻi faʻapipiʻi saʻo fesoʻotaʻiga nofoaga e taua tele foi, pe afai e le mafai ona faʻavaeina lelei le eleele mo mafuaaga eseese, o le a maualuga le malosi o le uaea i le tele o kilovolts e oo lava i le fiasefulu afe o volts. , e faigofie ona taʻitaʻia i fafo o le faʻamaʻi malepe ma faʻaauau le faʻamalo, mafua ai le maualuga o le vevela o le uaea pito i fafo poʻo le mu foi.
GDCO-301 faʻaaogaina le auala faʻasalalau o loʻo iai nei.Pe a o'o i lalo o tulaga masani le fa'alava uaea-autu (e tasi le mata'i), o lo'o ta'amilo i luga o le fa'afu, e tele lava le capacitive current, e matua la'ititi lava.O le taimi lava e tupu ai le tele-point earthing i luga o le u'amea u'amea ma fai ai se matasele, o le a fa'atupula'ia tele le tafega ma e mafai ona o'o atu i le sili atu i le 90% o le taimi autu.O le mataʻituina o le faʻasologa o le uʻamea ma ona suiga e mafai ona iloa i luga ole laiga le mataʻituina o le tele-point earth fault o le tasi-core cable sheath, ina ia vave ma saʻo ona maua le faaletonu o le eleele, e aloese mai le tupu mai o faʻalavelave faʻafuaseʻi ma faʻamautinoa le saogalemu ma le faʻatuatuaina o le gaioiga.
E faʻaaogaina le GSM poʻo le RS485 e avea ma auala fesoʻotaʻiga.E fetaui lelei mo le mataituina o faaletonu eleele e tele o laina autu e tasi i luga atu o le 35kV.
GDCO-301 Online Monitoring System of Circulating Current on Cable Sheath e aofia ai: iunite autu o masini mata'itū tu'ufa'atasi ma le suiga o lo'o i ai nei, vevela ma le leo gaoi.O lo'o fa'apipi'iina le fa'aliliuga o lo'o i ai nei i luga o le laina o le fa'alava uaea ma fa'aliliuina i se fa'ailoga lona lua a'o le'i fa'aofiina le masini mata'ituina.O le masini vevela e faʻaaogaina e mataʻituina ai le vevela o le uaea, ma le faʻaogaina o le gaoi e faʻaaogaina e mataʻituina ai le laina faʻavae.O le tu'ufa'atasiga o faiga mata'ituina i luga ole laiga o fa'alava uaea e fa'apea:
●Mata'ituina taimi moni o le taimi nei o le tolu vaega o le uaea, le aofa'i o le eleele ma le fa'aogaina o so'o se vaega uaea autu;
●Mataituina taimi moni o le vevela o le uaea tolu vaega;
●Taimi moni e tete'e - gaoi mata'ituina o le fa'avae uaea;
●E mafai ona seti taimi vaeluaga;
●Fa'amaufa'ailoga fa'ailo ma pe fa'ataga le mata'ituina fa'atatau e fa'atupu fa'ailo e mafai ona seti;
●Seti le tau maualuga, tau maualalo ma tau averesi i le vaitaimi faatulagaina;
●Mata'ituina taimi moni o le fua faatatau o le maualuga ma le tau maualalo o le tasi-vaega eleele i le taimi nei i totonu o le vaitaimi fa'afuainumera, ma le fa'agasologa o fa'ailo;
●Mata'ituina taimi moni o le fua faatatau o le eleele i le taimi nei e uta i totonu o le vaitaimi fa'afuainumera, ma le fa'agasologa o fa'ailo;
●Mata'ituina taimi moni o le suiga o le fua faatatau o le eleele i le taimi nei i totonu o le vaitaimi fa'afuainumera, ma le fa'agasologa o fa'ailo;
●E mafai ona lafoina faʻamatalaga fua i soʻo se taimi.
●E mafai ona faʻamaonia se tasi pe sili atu mataʻituina taʻiala e faʻafefe, auina atu faʻamatalaga faʻailoga i le telefoni feaveaʻi;
●Fuafuaga taimi tonu o le voluma ulufale;
●O fa'amatalaga mata'ituina uma e iai fa'ailoga taimi e fa'amautinoa ai le tulaga ese o fa'amaumauga;
●O masini mataʻituina uma e mafai ona faʻatulagaina e tusa ai ma manaʻoga o tagata faʻaoga;
●Tele fesoʻotaʻiga faʻasalalauga faʻamatalaga: RS485 interface, GPRS, GSM SMS, e mafai ona faʻaogaina se tasi pe sili atu faʻasalalauga faʻamatalaga i le taimi e tasi;
●Lagolago le tausiga mamao ma le faʻaleleia;
●Fuafuaga o le faʻaogaina o le eletise maualalo, lagolago le tele o faʻaogaina o le eletise: CT induction power, AC-DC mana ma le malosi o le maa;
●Fa'atasi ai ma vaega tau alamanuia, fa'atasi ai ma le fa'atuatuaina lelei ma le mautu;
●Modular faʻapipiʻi atoatoa fausaga, faigofie ona faʻapipiʻi, lokaina faiga e faia i vaega uma, lelei anti-vibration faatinoga, ma faigofie ona sui ma disassemble;
●Lagolago tulaga puipuia IP68.
Aitema | Parameter | |
I le taimi nei
| Fa'agaoioi le taimi nei | 1 alavai, 0.5~1000A (E mafai ona faʻatulagaina) |
A'a o le eleele | 4 alavai, 0.5~200A (E mafai ona faʻatulagaina) | |
Sa'o le fua | ±(1%+0.2A) | |
Vaitaimi fua | 5~200s | |
vevela | Avanoa | -20℃~+180℃ |
Sa'o | ±1℃ | |
Vaitaimi fua | 10~200s |
RS485 uafu
●Baud rate: 2400bps, 9600bps ma 19200bps e mafai ona seti.
●Umi o fa'amaumauga: 8 bit:
●Amata bit: 1 bit;
●Taofi fasi: 1 bit;
●Fa'avasegaina: leai se fa'avasegaina;
GSM/GPRS uafu
●Auala galue: Quad-band, 850 MHz/900 MHz/1800 MHz/1900 MHz;
●GSM Saina/Igilisi fe'au pupuu;
●GPRS vasega 10, Max.saosaoa la'uina 85.6 kbit/s, Max.tuʻuina atu le saoasaoa 42.8 kbit / s, lagolago TCP / IP, FTP ma HTTP protocol.
Paoa sapalai
AC sapalai eletise
●Malosiaga: 85 ~ 264VAC;
●Auala: 47 ~ 63Hz;
●Malosiaga: ≤8W
Ma'a
●Malosiaga: 6VDC
●Malosiaga: fuafua ile taimi galue faifai pea ole maa
●Ma'a fetaui
Fa'asalaina fa'aeletise fa'agata | Vasega 4:GB/T 17626.2 |
Leitio fa'avevesi fa'aeletise fa'amaneta fa'avevela fa'avevela | Vasega 3:GB/T 17626.3 |
Fa'aeletise vave le tumau/pa'u puipuiga | Vasega 4:GB/T 17626.4 |
Si'itia le puipuiga | Vasega 4:GB/T 17626.5 |
Leitio fa'atosina fa'aoso fa'aoso i luga ole alaleo | Vasega 3:GB/T 17626.6 |
Malosi fa'avevela fa'amaneta puipuiga | Vasega 5:GB/T 17626.8 |
Malosi fa'amaneta fa'amaneta | Vasega 5:GB/T 17626.9 |
Fa'asa'o fa'afefete fa'amaneta fa'agata | Vasega 5:GB/T 17626.10 |
Fa'asinomaga tulaga:
Q/GDW 11223-2014: Fa'amatalaga Fa'apitoa mo le su'esu'eina o le setete mo laina uaea eletise maualuga
4.1 E mafai ona vaevaeina le iloa o le cable state i ni vaega se lua: su'esu'ega i luga ole laiga ma le su'esu'eina tuusao.O le mea muamua e aofia ai infrared su'esu'ega, eleele i le taimi nei su'esu'ega o le fa'a'afu uaea, vaega tu'uina atu su'esu'ega, a'o le tui fa'asalalau o lo'o i ai se vaega fa'amalo i lalo ole su'esu'ega fa'asolo fa'asologa fa'asolosolo, oscillation cable fa'asa'o vaega.
4.2 O auala e iloa ai uaea e aofia ai su'ega lautele i luga o se fua tele, toe su'esu'e i fa'ailoga masalomia, fa'ata'ita'i fa'atatau i masini fa'aletonu.I lenei auala, e mafai ona mautinoa le faagaoioiga masani uaea.
4.3 E tatau i le aufaigaluega su'esu'e ona auai i a'oa'oga fa'apitoa mo le su'esu'eina o uaea ma umia nisi tusi pasi.
4.4 Fa'avae mana'oga mo le fa'ata'ita'iga fa'aa'ai fa'alava ma le fa'aogaina o le eleele o lo'o fa'asino ile Fa'aopoopoga A. Mana'oga autu ole su'esu'eina ole vaega ole voluma maualuga, ole su'esu'ega ole vaega ole alu ole eletise ma le su'esu'ega ole vaega ole ultrasonic ile Q/GDW11224-2014.
4.5 Va'aiga o talosaga e fa'asino ile Siata 1.
Metotia | Voltage grade o le uaea | Fa'ailoga autu e iloa ai | faaletonu | Initoneti/le initaneti | Fa'amatalaga |
Ata infrared vevela | 35kV ma luga atu | Terminal, so'oga | Le lelei le feso'ota'iga, fa'asusu, fa'aletonu fa'alava | Initoneti | Fa'amalosia |
Uamea fa'alava o le eleele | 110kV ma luga atu | Fa'aeleele | Fa'aletonu fa'alava | Initoneti | Fa'amalosia |
Fa'asao maualuga fa'ase'e | 110kV ma luga atu | Terminal, so'oga | Fa'aletonu fa'alava | Initoneti | Fa'amalosia |
Fa'ato'a fa'ate'a fa'atasi | 110kV ma luga atu | Terminal, so'oga | Fa'aletonu fa'alava | Initoneti | Filifili |
Galulu Ultrasonic | 110kV ma luga atu | Terminal, so'oga | Fa'aletonu fa'alava | Initoneti | Filifili |
Tu'u vaega i lalo ole su'ega fa'asolosolo fa'asolosolo fa'asolosolo | 110kV ma luga atu | Terminal, so'oga | Fa'aletonu fa'alava | Le Initaneti | Fa'amalosia |
OWTS oscillation cable fa'asa'oloto vaega | 35kV | Terminal, so'oga | Fa'aletonu fa'alava | Le Initaneti | Fa'amalosia |
Laulau 1
Vasega voluma | Vaitaimi | Fa'amatalaga |
110(66)kV | 1. I totonu ole 1 masina pe a uma le taotoga poʻo le toe faʻaleleia tele 2. E tasi mo le isi 3 masina 3. Pe a manaomia | 1. E tatau ona fa'apu'upu'u le taimi e iloa ai pe a mamafa le uta i luga o laina uaea po'o le taimi o le taumafanafana. 2. E tatau ona faia soo le su'esu'ega e fa'atatau i le leaga o le si'osi'omaga o galuega, masini tuai, ma masini fa'aletonu. 3. E tatau ona faia fetuunaiga talafeagai e fa'atatau i tulaga o masini ma le siosiomaga o galuega. 4. Fa'ainitaneti le mata'ituina o le eleele o lo'o i luga o le uaea e mafai ona sui ai lona su'esu'ega ola. |
220kV | 1. I totonu ole 1 masina pe a uma le taotoga poʻo le toe faʻaleleia tele 2. E tasi mo le isi 3 masina 3. Pe a manaomia | |
500kV | 1. I totonu ole 1 masina pe a uma le taotoga poʻo le toe faʻaleleia tele 2. E tasi mo le isi 3 masina 3. Pe a manaomia |
Laulau 4
5.2.3 Ta'iala mo su'esu'ega
E mana'omia le tu'ufa'atasia o le uta uaea ma le fa'aletonu o lo'o iai nei o le fa'alava uaea fa'atasi ai ma fa'amaumauga o le fa'alava uaea.
O ta'iala mo su'esu'ega e fa'asino ile Laulau 5.
Su'ega | I'uga | Fautuaga |
Afai e ausia uma manaʻoga o loʻo i lalo: 1. Taua atoatoa o le taimi o le eleele<50A; 2. O le fua faatatau i le va o le taimi nei o le eleele ma le uta<20%; 3. Max.tau/ Min.tau o le vaega tasi le taimi o le eleele<3 | masani | Fa'agaoioi e pei ona masani ai |
Afai e ausia soʻo se manaʻoga o loʻo i lalo: 1. 50A≤tau aoga atoatoa o le eleele i le taimi nei ≤100A; 2. 20%≤le fua faatatau i le va o le eleele i le taimi nei ma uta ≤50%; 3. 3≤Max.tau/Min.tau o le vaega tasi eleele current≤5; | Fa'aeteete | Fa'amalosia le mata'ituina ma fa'apu'upu'u taimi e iloa ai |
Afai e ausia soʻo se manaʻoga o loʻo i lalo: 1. Taua atoatoa o le taimi o le eleele>100A; 2. Le fua faatatau o le taimi nei eleele ma uta>50%; 3. Max.tau/Min.tau o le vaega tasi le taimi o le eleele>5 | faaletonu | Pepe ma siaki. |
Laulau 5