GDSF-311WPD 3-I-1 SF6 Su'ega Gas
GDSF-311WPD (GDSF-411WPD) o se meafaigaluega lelei pe a manaʻomia le suʻeina o vai, mama ma faʻaleagaina oloa o le SF6 gas.Ole vaega autu ole su'ega ole sau ole DRYCAP® fa'asologa o masini na gaosia e le kamupani Finelani Vaisala.O le infrared principle SF6 gas purity testing sensor na gaosia e le European Sensor Company e faʻaaogaina e suʻe ai le mama o le SF6 gas.O le masini eletise na gaosia e Mombabo Company i Suiselani o loʻo faʻaaogaina e fai ma elemene faʻalogo mo le suʻega o oloa faʻaleagaina o le kesi SF6.Faatasi ai ma tupe meataalo faʻapolofesa faʻapolofesa ma algorithms polokalama sili ona lelei o STMicroelectronics, ua matou gaosia se augatupulaga fou o le 3-in-1 gas analyzer.
SF6Susū
●Metotia fua: Resistive ma Capacitive fua faʻavae mataupu faavae
●Fua fuaina: sau -80℃--+20℃(lagolago ppmv)
●Sa'o: ±1℃
(pe a o'o i lalo ifo le 0 ℃ le vevela o le sau, o le mea e maua ai le masini o le aisa lea)
●Taimi tali: 63% [90%]
+20→-20℃ Td 5s[45s]
-20→-60℃ Td 10s[240s]
●I'uga: 0.01℃
●Toe fai: ± 0.5 ℃
●Fa'aaliga iunite: ℃, ppm, ℃P20(fa'aliliuina tau ile 20℃)
●Fa'amama kesi: 400-600ml / min
●Fa'aaliga tafe: 0-1000mL mita fa'afuainumera
●Fa'ata'ita'iga kesi mamafa: ≤1MPa
SF6mama
●Auala e fua ai: Fa'avae Fa'atatau o le Infrared Measurement Principle (NIR series sensors)
●Fua fuaina: 0 ~ 100% SF6
●Taimi tali: [90%] 60s
●Sa'o: ± 0.5%FS
●Toe fai: ± 0.5%
●I'uga: 0.01%
●Fa'aaliga iunite:%
SF6Oloa Fa'aleagaina
●Fua Fa'atatau: Fa'avae Fa'atatauga Fa'aeletise (Senesini fa'asologa o mea tau eletise)
●Va'aiga fua: H2S: 0 ~ 200ppmv
SO2: 0 ~ 200ppmv
CO: 0 ~ 500ppmv
HF: 0 ~ 50ppmv
●Sa'o: H2S: 10ppmv ±3%
SO2: 10ppmv ±3%
CO: 50ppmv ±4%
HF: 10ppmv ±3%
●Toe fai: H2S: 10ppmv ±2%
SO2: 10ppmv ±2%
CO: 50ppmv ±2%
HF: 10ppmv ±2%
●I'uga: 0.01ppmv
●Fa'aaliga iunite: ppmv
●Malosiaga tuʻuina atu: 220VAC±10%, 50Hz, AC / DC faʻaoga, puipuiga o le totogi, faʻaauau le galue e le maualalo ifo i le 8hours.
●Fa'aoga le vevela o le siosiomaga: -20--+60 ℃
●Siosiomaga susū: 90%RH
●A'afiaga tau fua: Leai se a'afiaga o le mamafa ma le tafe
●Fua: 395*295*155mm
●Mamafa: e tusa ma le 2kg.
GDSF-411WPD SF6Oloa Fa'aleagaina
●Sa'o: H2S: <10ppmv ±0.3ppmv;>10ppmv ±3%
SO2: <10ppmv ±0.3PPmv;>10ppmv ±3%
●Toe fai: H2S: <10ppmv ±0.2ppmv;>10ppmv ±2%
SO2: <10ppmv ±0.2PPmv;>10ppmv ±2%
●Toe fa'aleleia ma fa'atumu galuega: potu toe fa'aaogaina 2L,taimi toe fa'aaogā ≤ 5min
Fa'atasi ai ma galuega fa'agogo kasa
●Fua: 395*295*315mm
●Mamafa: e tusa ma le 5kg.
Su'e Autu | 1 fasi |
Fetuuna'i | 1 seti |
Teflon paipa (aofia ai le tafe fetuutuunai valve ma soʻotaga vave) | 1 seti |
Pipa si'usi'u | 1 seti |
Vaega fa'apitoa | 1 seti |
Totogi | 1 fasi |
Tagata fa'aoga's Taiala | 1 fasi |
Lipoti o Su'ega | 1 fasi |